Nine 2023 NEC code changes electricians need to know (2024)

GFCI 210.8

Sections 210.8(A) and 210.8(B) expanded GFCI to protect all receptacles found in the kitchen. To address appliances that are hard wired, section 210.8(D) was expanded to include more appliances such as electric ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and microwave ovens. eaton-gfci-mm.pngThe theme of addressing hard wired, non-cord-and-plug-connected equipment, was carried over to expansions found in 210.8(F) for outdoor outlets.
 
Download Eaton's infographics to visually learn about important changes to  GFCI requirements for residential kitchens and recommended receptacles to meet the code changes.
 

Surge (230.67, 215.18, 225.42)

Surge is required for services supplying dormitory units, guest rooms and guest suites of hotels and motels, and areas of nursing homes and eaton-surge-proteection.pnglimited-care facilities used as patient sleeping rooms. Additionally, surge requirements were placed in article 215 for feeders and article 225 for outdoor branch circuits and feeders. Lastly, a new requirement creates a minimum nominal discharge current rating (In) of 10kA.
 

Barriers (215.15)

New section 215.15 was added to address the increased risk for panelboards, switchboards, switchgear, or motor control centers that are supplied by the secondaries of transformers and feeder tap conductors. Barriers are now needed eaton-barriers-panel.pngso that no energized, uninsulated, ungrounded busbar or terminal is exposed to inadvertent contact by persons or maintenance equipment while servicing load terminations.
 

Cybersecurity (110, 240.6D, 708.7, 708,8A)

Cybersecurity is now included in the national electrical code. Systems that perform a life safety function and are connected to the network, circuit breakers connected eaton-nec-cyber.pngto a network that can have their set points changed remotely and equipment in a critical operation power system that is connected to the network must be evaluated for cybersecurity risks.
 

Service Equipment (230.71)

Meter centers are still included in 230.71 language to permit multiple over current devices in the same structure, but recent UL67 changes have eaton-nec-service.pngbeen made so that equipment can be constructed and circuit breakers can be compartmentalized so barriers can be placed on the line side.
 

Arc Flash Labeling (110)

Section 110.16(B) was expanded beyond just services and beyond services rated 1200 amps and above. This section now requires labeling for services and feeder supplied equipment rated 1000 amps and above. These requirements only affect other than dwelling units.
 

Reconditioned Equipment (100)

The 2023 code moved all definitions to article 100. Code making panels coordinated an effort to include reconditioning requirements in the nnn.2 sections of the articles. This consistency is an important part of usability for the national electrical code.

 

Receptacles in Islands and Peninsulas (210.52)

The 2023 code cycle made the placement of a receptacle on islands and peninsulas optional, but provisions must be put in place to ensure it can be added in the future. In addition, the receptacle must be on or in the countertop to avoid chords of appliances draping over the edge of the countertop.

 

Selective Coordination

Selective coordination has historically in the code been addressed by areas of the NEC focused on life safety systems such as article 700. Informational notes in these articles where selective coordination is required, added clarity that the requirements are only for overcurrent protective devices that are in, for example, the life safety system.
 